Spray-applied fire-resistive material (SFRM) remains one of the most important yet least understood elements of building safety. It protects structural steel from heat, delays failure during a fire, and helps maintain a building’s integrity long enough for people to evacuate and for firefighters to respond.

In a city built on steel, this often-overlooked layer of protection plays a key role in structural safety. Awareness of how SFRM should be specified is growing as codes and standards continue to evolve, but gaps in understanding can still lead to challenges during design review, inspection, or emergency response.

Misconceptions in fireproofing design continue to cause specification and performance issues. The following are five of the most common.

The Myths Behind the Material

Fireproofing is often mistaken for a surface coating or decorative finish. In reality, spray-applied fire-resistive material (SFRM) is an engineered system designed to insulate structural steel from extreme heat. Without this layer, steel can begin to lose strength at roughly 572°F and reach failure near 1,000°F.

Once applied, SFRM forms a barrier that slows heat transfer, providing valuable minutes for evacuation and fire response. In a dense, vertical city like New York, those minutes can determine whether a structure remains stable or collapses.

Five Common Misconceptions

Despite its importance, several myths persist across the design and construction industry:

  1. Cementitious fireproofing always contains Portland cement. Not necessarily. Some cementitious materials use gypsum binders. The classification refers to how the material behaves and is applied, not its specific chemical makeup.
  2. Fibrous and cementitious SFRMs are interchangeable. They are not. Cementitious materials have a higher binder content, often up to 80 percent, and are mixed with water to create a dense, uniform slurry. Fibrous fireproofing uses mineral wool with about 20 to 30 percent binder and is applied as a dry mix with water introduced at the nozzle. These differences affect density, adhesion, and performance.
  3. All SFRMs perform the same. Performance depends on bond strength, which is defined by the New York City Building Code. Buildings up to 420 feet require a minimum bond strength of 430 pounds per square foot, while those taller than 420 feet require 1,000 pounds per square foot. Higher bond strength products are also used in transit facilities, infrastructure, and industrial environments where vibration or impact is expected.
  4. Restrained and unrestrained systems are the same. They are not. Under ASTM E119 and UL 263, restrained assemblies perform differently when exposed to heat. The design professional must document the correct classification on the structural drawings and in the specifications.
  5. Fireproofing is a finishing step. It is not. SFRM is a life-safety system that protects structural members, slows heat transfer, and extends structural stability under fire exposure.

Each of these misconceptions carries consequences. Misapplied or misidentified fireproofing can lead to failed inspections, code violations, and reduced performance during a fire.

What Design Professionals Should Know

Accurate fireproofing design begins well before installation. Understanding how SFRM systems are classified, tested, and specified helps architects, engineers, and specifiers confirm that each project achieves its intended fire-resistance rating.

Considerations include:

  • Selecting the correct SFRM type and bond strength for the structural system and building height.
  • Coordinating UL design numbers and required thicknesses within drawings and specifications.
  • Verifying restrained or unrestrained classifications under ASTM E119 or UL 263.
  • Requiring field testing and inspection in accordance with the New York City Building Code.

New York City’s Local Law 26 of 2004 mandated sprinkler systems in office and business-occupancy buildings 100 feet or taller, with full compliance achieved by July 1, 2019. That law addressed active fire suppression, while passive systems such as SFRM remain essential to the city’s broader fire-protection strategy.

With Local Law 97 now in effect as of May 1, 2025, the city’s focus extends to energy performance and carbon reduction in buildings over 25,000 square feet. As owners retrofit properties to meet new emissions limits, walls and ceilings are often opened for insulation and system upgrades. When structural steel or rated assemblies are exposed during this work, fireproofing must be restored to maintain life-safety compliance and pass inspection.

Together, these codes promote a coordinated approach that combines active systems like sprinklers, passive systems like SFRM, and energy-efficiency measures, all contributing to safer, more resilient, and sustainable buildings across New York City.

Fire Prevention Month Reminder

Fire Prevention Month is a time to focus on what protects the structure itself. SFRM is not a finishing step; it is part of the building’s life-safety system. When properly specified, installed, and inspected, it works alongside sprinklers, alarms, and egress design to meet performance standards and maintain compliance for the life of the building.